UNIFIED PROPORTIONAL INTEGRAL DERIVATIVE LOAD FREQUENCY CONTROL VIA PARTICLE SWARM AND HYBRID PARTICLE SWARM MODEL PREDICTIVE OPTIMIZATION FOR HYDRO THERMAL POWER SYSTEMS

Frequency regulation in hydro–thermal systems is complicated by the slow reheat dynamics of steam units and the non-minimum-phase response of hydro penstocks. This paper develops a unified proportional–integral–derivative (PID) load frequency control (LFC) scheme, in which a single set of secondary gains serves both control areas, and tunes it with standard particle swarm optimization (PSO) and with a hybrid PSO–model predictive control (PSO–MPC) framework. The test system is a 1500 MW two-area network: Area 1 holds two 500 MW reheat tandem-compound steam units and Area 2 a single 500 MW hydro unit, linked by a tie-line. Instead of textbook defaults, the steam-chest, reheater and crossover time constants (0.36 s, 5.09 s and 0.40 s) and the turbine stage power fractions (0.273, 0.351 and 0.376) were derived from the heat balance diagram of a 500 MW unit and interpolated superheated-steam tables. The PSO objective was the integral of time-weighted absolute frequency error (ITAE) summed over both areas. Responses to 1.0 Pu. step load disturbances were simulated in MATLAB/Simulink R2023b and compared with a Ziegler–Nichols (Z-N) baseline. The Z-N controller kept the system stable but left a persistent frequency offset of 0.005–0.009 Hz, whereas both optimized controllers returned the frequency to 50 Hz. The hybrid PSO–MPC scheme reached an ITAE cost of 297.99 against 422.18 for standard PSO, a 29.4% reduction, with the smallest Area 1 undershoot, although its transient advantage over PSO was small. A single coordinated gain set therefore suffices for a mixed hydro–thermal system, without area-specific tuning.

Authors : Adamu, A.S., Jival, A., Aminu, M., Musa, S.Y. and Usman, S.I.

Category : Open Access     Volume (Issue) : 12(1)     Date Uploaded : 9th October 2026

Download Copy

CONTACT US

Feel free to contact 24X7

Mailing address:
Office of the Dean, SEET MAUTECH, PMB 2076, Yola, Adamawa State.

+234 8063124156

MailID: [email protected]

SEND US A COMMENT

© 2026. NJESTR design by TIN Technologies